Product Name£ºPM60 3PH Rack Module UPS PM60K RM
     
    Key Features


    ¡ôPower Module 60K Rack Module UPS 120K/180K/240K/300K/480K/600K
    ¡ôHigh effciency over 94.5% at 50% load, Output Power Factor 1 technology
    ¡ôDSP control, online double conversion, Integrated modular and parallel technology
    ¡ôHigh scalability,Single rack expanding 120KVA to 600KVA, N+1 or N+X redundancy in the same rack, supports 1+1 cabinet parallel operation.
    ¡ôBuilt-in maintenance bypass, praevia all panel control and connectors
    ¡ôHighly reliable operation with redundant power supply(2) in STS
    ¡ôHigh overload Capacity , 110%@ 60mins, 125%@10Mins,150%@1mins
    ¡ô32 to 40PCS adjustable Battery numbers
    ¡ôAdiustable charging current,Max 18A

    Technical Specifications


    MODEL

    RM120/60X30U-RYY

    RM180/60X30U-RYY

    RM240/60X-RYY

    RM300/60X-RYY

    RM480/60X42U-RYY

    RM600/60X42U-RYY

    PHASE

    3-phase in/3-phase out

    CABINET CAPACITY *

    120KW

    180KW

    240KW

    300KW

    480KW

    600KW

    BATTERY TYPE

    External Battery

    One Power Module
    Capacity

    60KVA/60KW

    Max. Power Module No.

    2

    3

    4

    5

    8

    10

    INPUT

    Nominal Voltage

    3 x 380VAC/400VAC/415VAC (3Ph+N)

    Voltage Range

    305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load

    Nominal Frequency

    50/60Hz (Auto sensing)

    Frequency Range

    40Hz ~70Hz

    Power Factor

    > 0.99 at 100% load, >0.98 at 50% load

    Harmonic Distortion (THDi)

    < 3% @ 100% load

    OUTPUT

    Nominal Voltage

    3 x 380VAC/400VAC/415VAC (3Ph+N)

    Voltage Regulation (Steady state)

    ¨Q¡À 1% Typical (balanced load)
    ¨Q¡À 2% Typical (unbalanced load)

    Nominal Frequency

    50/60Hz

    Frequency Range
    (Synchronized range)

    46Hz ~ 54Hz or 56Hz ~ 64Hz

    Overload Capability

    1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%

    Harmonic Distortion

    ¨Q 2% THD (Linear Load)
    ¨Q 4% THD (Non-linear Load)

    Efficiency

    Up to 96%

    BATTERY/ CHARGER

    Nominal Voltage

    +/- 192V~+/- 240V (Selectable)

    Maximum Voltage

    +/- 240V (12V x 40 Pcs)

    Minimum Voltage

    +/- 192V (12V x 32 Pcs)

    Floating Charge Voltage

    2.28V/Cell (2.25~2.33 Selectable)

    Boost Charging Voltage

    2.35V/Cell

    Temperature Compensation

    Yes

    Maximum Charging Current (Per Power Module)

    18A

    PHYSICAL

    Cabinet Dimension
    (D x W x H) mm

    1100 x 600 x 1475

    1100 x 600 x 2010

    1065 x 1000 x 2000

    Net Weight (kgs)

    308

    352

    516

    516

    932

    1020

    ENVIRONMENT

    Operation Temperature

    0 ~ 40¡æ

    Relative Humidity

    0 ~ 95% non-condensing

    Altitude*

    <1000m for Nominal power

    IP Class

    IP 20

    MANAGEMENT

    RS-232/USB

    Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC

    Optional SNMP

    Power management from SNMP manager and web browser

    STANDARDS

    Safety

    IEC/EN 60950-1; IEC/EN 62040-1

    EMC

    IEC/EN 62040-2 Category C3

    *If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.

    Model

    Description

    Dimension DxWxH(mm)

    Weight (kg)

    PM-60

    3P/3P 60KVA60KW power module

    750 x 438 x 133 (3U)

    44

     

     
     

    Tel: 0086-574-88216630    Fax: 0086-574-8813 8440    Email: kema@kemapower.com
    Factory:H/Block Beiyue Industrial Zone,Foshan,China.
    Ningbo office:R505-1,TAIKANG MIDDLE ROAD 468#,YINZHOU DISTRICT, NINGBO,CHINA
    ?2004-2018 Kemapower Electronics Co., LTD.    All rights reserved