MODEL |
RM 300/50 XS - RYY |
RM 300/50X- RYY |
RM 350/50X- RYY |
RM 400/50X- RYY |
RM 500/50X- RYY |
PHASE |
3-phase in/3-phase out |
CABINET CAPACITY* |
300KW |
300KW |
350KW |
400KW |
500KW |
BATTERY TYPE |
External Battery |
One Power Module
Capacity |
50KVA/50KW |
Max . Power Module No . |
6 |
6 |
7 |
8 |
10 |
INPUT |
Nominal Voltage |
380VAC/400VAC/415VAC (3Ph+N) |
Voltage Range |
305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load |
Nominal Frequency |
50/60Hz (Auto sensing) |
Frequency Range |
40Hz ~70Hz |
Power Factor |
> 0.99 at 100% load, >0.98 at 50% load |
Harmonic Distortion (THDi) |
< 4% @ 100% load |
OUTPUT |
Nominal Voltage |
380VAC/400VAC/415VAC (3Ph+N) |
Voltage Regulation (Steady state) |
¨Q¡À 1% Typical (balanced load)
¨Q¡À 2% Typical (unbalanced load) |
Nominal Frequency |
50/60Hz |
Frequency Range
(Synchronized range) |
46Hz ~ 54Hz or 56Hz ~ 64Hz |
Overload Capability |
1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150% |
Harmonic Distortion |
¨Q 2% THD (Linear Load)
¨Q 4% THD (Non-linear Load) |
Efficiency |
Up to 95.5% |
BATTERY/ CHARGER |
Nominal Voltage |
+/- 192V~+/- 240V (Selectable) |
Maximum Voltage |
+/- 240V (12V x 40 Pcs) |
Minimum Voltage |
+/- 192V (12V x 32 Pcs) |
Floating Charge Voltage |
2.28V/Cell (2.25~2.33 Selectable) |
Boost Charging Voltage |
2.35V/Cell |
Temperature Compensation |
Yes |
Maximum Charging Current (Per Power Module) |
12A |
PHYSICAL |
Cabinet Dimension
(D x W x H) mm |
850 x 600 x 2000 |
1065 x 600 x 2010 |
1065 x 600 x 2010 |
1065 x 1000 x 2010 |
1065 x 1000 x 2010 |
Net Weight (kgs) |
490 |
545 |
654 |
932 |
1020 |
ENVIRONMENT |
Operation Temperature |
0 ~ 40¡æ |
Relative Humidity |
0 ~ 95% non-condensing |
Altitude* |
<1000m for Nominal power |
IP Class |
IP 20 |
MANAGEMENT |
RS-232/USB |
Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC |
Optional SNMP |
Power management from SNMP manager and web browser |
STANDARDS |
Safety |
IEC/EN 60950-1; IEC/EN 62040-1 |
EMC |