Product Name£º | PM20 PM30 3PH Rack Module UPS PM20-30K RM |
Features |
¡ô Power Module 20K 30K Rack Module UPS 80k/90K/120K/120K/200K/210K/300K
¡ô High effciency over 94.5% at 50% load, Output Power Factor 1 technology
¡ô DSP control, ,online double conversion,Integrated modular and parallel technology
¡ô High scalability,Single rack expanding 30KVA to 300KVA,N+1 or N+X redundancy in the same rack, supports 1+1 cabinet parallel operation.
¡ô Built-in maintenance bypass, praevia all panel control and connectors
¡ô Highly reliable operation with redundant power supply(2) in STS
¡ô High overload Capacity , 110%@ 60mins, 125%@10Mins,150%@1mins
¡ô 32 to 40PCS adjustable Battery numbers
¡ô Adiustable charging current,Max 8A or 6A/Module
¡ô Graphic 5.7" LCD design for easy management
¡ô Optional 10" touch LCD panel, Optional SNMP
|
|
 |
|
MODEL |
RM90/30X-RYY |
RM120/30X-RYY |
RM120/30X-RYY
RM80/20X-RYY |
RM180/30X-RYY RM120/20X-RYY |
RM200/20X-RYY |
RM210/30X-RYY |
RM300/30X-RYY |
PHASE |
3-phase in/3-phase out |
CABINET CAPACITY* |
90KW |
120KW |
120KW or 80KW |
180KW or 120KW |
200KW |
210KW |
300KW |
BATTERY TYPE |
Built-in Battery |
External Battery |
One Power Module Capacity |
30KVA/30KW |
30KVA/30KW or 20KVA/20W |
20KW |
30KVA/30KW |
30KVA/30KW |
Max. Power Module No. |
3 |
4 |
4 |
6 |
10 |
8 |
10 |
Max. Battery Set No.** |
3 |
5 |
- |
- |
- |
- |
- |
INPUT |
Nominal Voltage |
380VAC/400VAC/415VAC (3Ph+N) |
Voltage Range |
305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load |
Nominal Frequency |
50/60Hz (Auto sensing) |
Frequency Range |
40Hz ~70Hz |
Power Factor |
> 0.99 at 100% load, >0.98 at 50% load |
Harmonic Distortion (THDi) |
< 3% @ 100% load |
OUTPUT |
Nominal Voltage |
380VAC/400VAC/415VAC (3Ph+N) |
Voltage Regulation (Steady state) |
¨Q¡À 1% Typical (balanced load)
¨Q¡À 2% Typical (unbalanced load) |
Nominal Frequency |
50/60Hz |
Frequency Range (Synchronized range) |
46Hz ~ 54Hz or 56Hz ~ 64Hz |
Overload Capability |
1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150% |
Harmonic Distortion |
¨Q2% THD (Linear Load)
¨Q4% THD (Non-linear Load) |
Efficiency |
Up to 94.5% |
BATTERY / CHARGER |
Nominal Voltage |
+/- 216V (12V x 36 Pcs) |
Maximum Voltage |
+/- 240V (12V x 40 Pcs) |
Minimum Voltage |
+/- 192V (12V x 32 Pcs) |
Floating Charge Voltage |
2.25V/Cell |
Boost Charging Voltage |
2.35V/Cell |
Temperature Compensation |
Yes |
Maximum Charging Current (Per Power Module) |
8A |
8A for 30KW power module
6A for 20KW power module |
6A |
8A |
8A |
PHYSICAL |
Cabinet Dimension
(D x W x H) mm |
1100 x 600 x 1475 |
1100 x 600 x 2010 |
1100 x 600 x 1475 |
1100 x 600 x 1475 |
1100 x 600 x 2010 |
Net Weight (kgs) |
675 |
932 |
335 or 333 |
437.5 or 434.5 |
611 |
549 |
620 |
ENVIRONMENT |
Operation Temperature |
0 ~ 40¡æ |
Relative Humidity |
0 ~ 95% non-condensing |
Altitude*** |
<1000m for Nominal power |
IP Class |
IP 20 |
MANAGEMENT |
RS-232/USB |
Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC |
Optional SNMP |
Power management from SNMP manager and web browser |
STANDARDS |
Safety |
IEC/EN 60950-1; IEC/EN 62040-1 |
EMC |
IEC/EN 62040-2 Category C3 |
|
*When temperature is above 30¡æ, the output power factor will be de-rated, 0.9 at 31¡æ~35¡æ and 0.8 at 36¡æ~40¡æ.
|
** one set = 4*Module (10*7AH/9AH Tray),Max 40PCS/set |
*** the altitude is above than 1000m, the output power must be derated one percent per 100m. |
 |
Model |
Description |
Dimension DxWxH(mm) |
Weight (kg) |
PM-30HV |
3P/3P 30KVA/30KW power module |
736.5 x 490 x 133 (3U) |
34.5 |
PM-20HV |
3P/3P 20KVA/20KW power module |
736.5 x 490 x 133 (3U) |
34 |
Battery Module |
10 pcs of 12V/9Ah or 7AH batteries |
710x107x154 |
26 (9AH) |
|

|
PM30 400V Cabinet |
Rack Model Name |
RM90/30X-RYY |
RM120/30X-RYY |
RM210/30X-RYY |
RM120/30X-RYY |
RM210/30X-RYY |
RM300/30X-RYY |
Height |
30U |
30U |
30U |
42U |
42U |
42U |
STS Capacity |
90K |
120K |
210K |
120K |
210K |
300k |
Type of installable
power module |
HV 30K or HV 20K |
HV 30K or HV 20K |
HV 30K or HV 20K |
HV 30K or HV 20K |
HV 30K or HV 20K |
HV 30K or HV 20K |
Max. number of installablepower module |
3 |
4 |
6 |
4 |
8 |
10 |
Number of installable battery modules in Layer |
3 |
N/A |
N/A |
5 |
N/A |
N/A |
Max. capacity of installing HV 20K module |
60K |
80K |
120K |
80K |
160K |
200K |
Max. capacity of installing HV 30K module |
90K |
120K |
180K |
120K |
210K (lf installed with 8 pcs,one is for redundancy) |
300K |
Max capacity winternalbattery, no external battery |
60K (Maximum with 3 layers of battery modules) |
N/A |
N/A |
90K (Maximum with 5 layers of battery modules) |
N/A |
N/A |
Built-in empty batterymodules in BOM |
Yes,12pcs |
No |
No |
Yes,20pcs |
No |
No |
|
|
PM20 400V Cabinet |
Rack Model Name |
RM90/20X-RYY |
RM120/20X-RYY |
RM210/20X-RYY |
Height |
30U |
30U |
42U |
STS Capacity |
90K |
120K |
210K |
Type of installablepower module |
HV 20K only |
HV 20K only |
HV 20K only |
Max.number ofInstallable power module |
4 |
6 |
10 |
Number of Installablebattery modules in layer |
N/A |
N/A |
N/A |
Max. capacity ofinstalling HV 20Kmodule |
80K |
120K |
200K |
Max.capacity ofinstalling HV 30Kmodule |
N/A |
N/A |
N/A |
Max capacity w/ intemalbattery, no external battery |
N/A |
N/A |
N/A |
|
|
|
|
|
|