Product Name£º | HIGH FREQUENCY ONLINE UPS XG 6k-20K SERIES |
¡ô LCD High frequency double conversion sine wave online UPS
¡ô DSP digital control technology, Zero transfer time
¡ô Single Phase Sine Wave, Output Power Factor 0.8/0.9 adjustable VAC and Hz by panel
¡ô Wide Input Voltage and Frequency Range, Support Generator
¡ô Advanced Input PFC Technology 0.99
¡ô Self-testing and battery management function
¡ô Automatic battery charging while UPS off mode
¡ô Lightning, Surge, Short Circuit and Overload Protection, Alarm or Silence Settable
¡ô RS232 or USB communication with monitoring software
¡ô SNMP, EPO, MBS optional |

|
Item |
Model |
XG6K |
XG10K |
XG15K |
XG20K |
Capacity |
VA / Watts |
6KVA / 5.4KW |
10KVA / 9KW |
15KVA /13.5KW |
20KVA /18KW |
Input |
Normal voltage |
220VAC |
Turn on Voltage range |
120¡«274VAC±5VAC |
Frequency range |
60Hz ± 2Hz |
Input power factor |
>0.99(220VAC,full R load) |
Generator |
Support generator input(Generator rating¡Ý2*UPS rating ) |
Output |
Voltage range |
200VAC/208VAC/220VAC/230VAC/240VAC, need confirm before order(Could be adjusted by software,10% derating for
208VAC/200VAC) |
Frequency range |
60Hz ± 2Hz |
Wave form |
Pure Sine Wave |
Transfer time |
0 ms, Between Line mode and Bat mode |
Transfer time: 4ms (typical 2.5ms), line Mode and bypass mode |
Voltage distortion |
¡Ü6%,Full RCD load |
Voltage distortion |
¡Ü2%,Full R load |
Overload capacity |
¡Ü105%+-5% warning only, 105%+-5%<Load¡Ü125% +-5%1ms to bypass ; 125%±5%<load¡Ü135%±5% 30S to bypass,
Load>135%±5% 100MS to bypass |
Load peak ratio |
3£º1£¨max£© |
Battery |
Battery Type |
Maintenance free valve regulated lead acid (VRLA) battery |
Battery Voltage |
240VDC |
Battery Capacity |
20*7AH |
20*7AH |
20*9AH |
20*9AH |
Recharge time |
3.5 hours to 90% capacity |
3.5 hours to 90% capacity |
5.5 hours to 90% capacity |
5.5 hours to 90% capacity |
Charge Current |
2.5A |
2.5A |
2.5A |
2.5A |
Display |
LED Display |
Line, Inverter, Bypass, Battery |
LCD Display |
LCD For input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp. Fault Code ,LED for line, bat, Inverter, Bypass, Fault |
Audible Alarm |
Battery Mode |
Beeping every 4 seconds (re-settable) and every second when battery low |
Overload |
Beeping twice every second |
Fault |
Beeping Continuously |
Battery low/charger fault |
Beeping every 1 second |
Bypass mode |
Beeping every 2 min |
L/N inverse |
Beeping every 2 min |
Communications |
RS-232/USB Interface |
RS232 or USB, with Monitoring |
Working Environment |
Surge protection |
RJ-45 I/O port available for network or Fax/Modem |
Working Temperature |
- 20¡æ~40¡æ |
Humidity |
0-95% non-condensing |
Product size |
WxDxH (mm) |
260*533*560 |
260*533*560 |
560*260*717 |
560*260*717 |
Product Weight |
Kg |
55/63(7AH) |
62/70(9AH) |
83(9AH) |
84(9AH) |
 |
 |
|
|
|