Item |
Model |
XG2K-407 |
Capacity |
VA/ Watts |
2KVA/2KW |
Input |
Nominal voltage |
220/230/240VAC |
Voltage range |
160-270VAC |
Frequency |
50/60Hz |
Frequency range |
45-65Hz |
Input power factor |
1.0 |
Generator |
Support generator input (Generator rating¡Ý2*UPS rating) |
Input power cord |
Detachable 1*line to line, 1*Neutral ground, 1*Earth ground (green) |
Output |
Nominal voltage |
220/230/240VAC |
Voltage regulation |
+/-1% |
Frequency range |
50Hz or 60HZ+-0.2Hz (Battery mode) |
Output power factor |
1.0 |
Wave form |
Pure Sine Wave |
Transfer time |
0 ms |
Crest factor |
3:1 of total harmonic distortion (THD) at linear load |
Harmonic distortion |
<3% of total harmonic distortion (THD) at linear load |
Overload capacity |
<105% warning only, <125% 30s; <150% 20s,>150%, 300MS to bypass |
Overload capability |
Able to sustain for at least 60sec. in case of 100% load without abnormal behavior of UPS |
Efficiency |
Minimum of 88% during AC mode
Minimum of 83% during battery mode |
Output outlet |
Standard design 3 prong parallel outlet 1*line to line, 1*Neutral ground, 1*Earth ground (green) |
Battery |
Battery type |
Sealed maintenance free valve regulated lead acid (VRLA) battery |
Battery runtime |
15mins (minimum) at ATM full load |
Recharge time |
5 hours to 90%capacity |
Charge current |
1A |
Display |
LED display |
Line, Inverter, Bypass, battery |
LCD display monitor |
LCD for Input Output Voltage Frequency, Bat %/VDC, Load in Watts, Temperature, Load Percentage,
LED for line, bat, Inverter, Bypass |
Audible Alarm |
Battery mode |
Beeping every 4 seconds (re-settable) and every second when battery low |
Overload |
Beeping twice every second |
Fault |
Beeping Continuously |
Battery low/charger fault |
Beeping every 1 second |
Bypass mode |
Beeping every 2 min |
L/N inverse |
Beeping every 2 min |
Communications |
RS-232/USB Interface |
RS232 or USB, With monitoring software |
Working Environment |
Surge protection |
RJ-45 I/O port available for network or Fax/Modem |
Operating temperature |
0¡æ-40¡æ |
Humidity |
0-95% non-condensing |
Protection |
Overload, Low input voltage, Surge input voltage per UL 1449, Overheat in the UPS |
Product Size |
WxDxH (mm) |
430*190*328(H) |
Product Weight |
Kg |
19 |